For a deep-well pump, choose the cable from the motor nameplate, the complete power-supply-to-motor route, the installation conditions and the motor maker’s voltage limits. Well depth or motor power alone cannot set the conductor size. A qualified electrician should verify the final cable and protection design against the exact motor instructions and local electrical rules.

Measure the complete cable route

Record the one-way cable path from the power supply or control panel to the motor: the surface cable section, the cable inside the well and any intermediate sections. Include the actual motor setting depth and extra length for bends and connections. A cable can carry rated current but still lose too much voltage over a long path. When using a manufacturer length chart, follow its definition of total length; do not double the length unless its method requires it.

Gather motor and installation data

Use the exact motor nameplate and manual. Confirm voltage, phase, frequency, rated current and starting or drive method. Record conductor material, insulation rating, water and air exposure, cable arrangement and splice locations. Check that the cable fits the well and is rated for submerged service where required.

Input Why it matters
Motor voltage, phase and rated current Sets the electrical duty and matching cable chart.
Total one-way cable length Controls resistance and voltage loss.
Cable type and wet/dry exposure Affects current capacity, insulation and installation suitability.
Starter, control box or drive Changes the motor and cable checks required at start-up.

Check current capacity and voltage drop

Confirm both current-carrying capacity and the voltage reaching the motor at the relevant operating condition. A larger conductor may be needed for voltage drop even when its ampacity is adequate. Use the motor manufacturer’s cable table or calculation method for the exact supply, motor and cable; check starting requirements and any drive-specific cable limits separately. Do not reuse another motor brand’s maximum cable length as a universal rule.

Prepare a cable and pump enquiry

Send the pump and motor nameplates, intended setting depth, full route sketch, power supply, starting method, cable construction, water temperature and required flow and head. Ask for the compatible cable size, splice arrangement and protection review before ordering.

  1. Measure the whole route, including the surface section.
  2. Check the actual motor manual and local electrical rules.
  3. Compare voltage drop and current capacity.
  4. Confirm submerged cable and splice suitability.

For product matching, see the deep-well pump range, use selection support, and send a quotation enquiry.

Frequently asked questions

These answers help define the data needed for a safe cable selection.

Can I size cable from pump horsepower alone?

No. Motor current, voltage, phase, route length, cable construction and installation conditions also matter.

Is well depth the same as cable length?

No. The cable from power supply to wellhead, the cable inside the well and extra length for bends and connections all count.