A sewage pump discharge check valve stops the liquid column or common header from flowing backward when the pump stops. Place it where the selected valve can operate in its approved orientation and can be inspected safely; confirm the location against the pump and valve manuals, station drawing and surge analysis. A fixed distance from the pump is not suitable for every wet well or force main.

What the check valve must do

In a single-pump line, reverse flow can refill the wet well and cause extra starts. In a duplex station, a stopped branch may also receive flow from the running branch. A check valve limits this reverse path; an isolation valve serves a different purpose by allowing a branch to be shut for maintenance. Show both valves, drain points, lifting access and the common header on one drawing. Do not assume a check valve is a safe isolation barrier for work.

Check the piping arrangement and orientation

The common sequence is pump discharge, check valve, then service isolation valve toward the header, but the exact position and allowable spacing depend on the manufacturer’s instructions and system hydraulics. Check the flow arrow, permitted vertical or horizontal mounting, required clearances, solids passage, pressure rating and access to the cover or hinge. Support the pipe independently. Include the valve’s head loss in the duty calculation. Fast closure, long rising mains and high flow velocity can produce pressure transients; selecting a nominally quiet valve alone does not replace a surge review.

Observed issue First checks
Wet well refills after stop Seat leakage, debris, alternate return path
Stopped pump branch flows backward Branch check valve and common-header arrangement
Valve slams at shutdown Velocity, closure behavior and surge conditions

Commission the valve and investigate symptoms

Before startup, verify the valve and pump rotation, open the required isolation valves, and follow the exact priming or venting procedure. Observe several controlled start-stop cycles and record wet-well levels, branch pressure, reverse-flow signs and closure noise. If the level rises immediately after shutdown, check for a leaking or obstructed seat, wrong installation direction, or an alternate return path. A slam can indicate flow reversal or a transient; inspect the full line before changing valve type. Isolate energy and pressure before opening a valve chamber.

  1. Mark flow direction and every check, isolation and drain valve on the as-built drawing.
  2. Confirm the valve’s permitted orientation, solids passage, materials and pressure rating.
  3. Compare pump duty with valve head loss and review shutdown transients.
  4. Record several starts and stops; investigate leakage or slam before ordering parts.

What to send for selection and service

For a replacement or new station, request the exact pump curve and valve instructions. DFIN can review the pump duty and layout, while the selected valve supplier must confirm its orientation, materials and limits. State whether the question concerns backflow, repeated starts, noise or planned maintenance; these require different checks.

Browse sewage pumps · Review selection support · Send a station enquiry

Frequently asked questions

Use the exact pump and valve instructions for installation and safe service.

Can an isolation valve replace a check valve?

No. An isolation valve is operated to shut a branch for service; a check valve responds automatically to reverse flow. The station may need both.

Does moving a check valve closer always stop water hammer?

No. Closure timing, flow velocity, pipe length and pressure profile matter. Verify the system transient and the valve manufacturer’s placement limits before moving it.